Standard
Auto / start / stop control
Engine cool-down timer
Environmental sealed front face
Emergency stop pushbutton
Text alarm / event descriptions
24 Volt DC operation
Controls:
Generator mounted - Rear facing
IVR includes reactive droop capability, 3-phase voltage sensing,
KVAR / PF modes, RFI suppression, min / max exciter.
Limiter and exciter diode monitor
Generator set packages include Caterpillar' s Voltage
Regulator.
EMCP 4.2B
Speed adjust
Alarm acknowledge
Engine cycle crank
Load histogram feature
Lamp test
Digital indication for:
Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
RPM
PLC functionality
Operating hours
Oil pressure (psi, kPa or bar)
Coolant temperature
DC volts
Power Factor (per phase & average)
Volts (L-L & L-N)
kW (per phase, average & percent)
Amps (per phase & average)
Frequency (Hz)
kVA (per phase, average & percent)
kVAr (per phase, average & percent
Low oil pressure - High coolant temperature
kVAr-hr (total)
High coolant temperature
Warning/shutdown with common LED indication of shutdowns for:
kW-hr (total)
Overspeed
Low coolant temperature
Failure to start (overcrank)
Emergency stop
Over/Under voltage (27 / 59)
Generator phase sequence
Low coolant level
Programmable protective relaying functions:
6 Customer programmable digital inputs
Over/Under Frequency (81 o/u)
Reverse Reactive Power (kVAr) (32RV)
Serial annunciator module data link
Reverse Power (kW) (32)
Number of I/O varies on options selected:
Overcurrent (50 / 51)
Cat Connect
4 Programmable relay outputs (Form A)
Communications:
Customer data link (Modbus RTU)
1 Programmable digital outputs
1 Programmable relay outputs (Form C)
Accessory module data link
3 Analog inputs