3516E Low Voltage Generator Set

3516E Low Voltage Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Request a Quote

Standby Rating3000 kVA (3100 kVA without fan)

Prime Power Rating2750 kVA (2850 kVA without fan)

Emissions/Fuel StrategyLow Fuel Consumption

Voltage380 to 11000 volts

Frequency50 Hz

Speed1500 rpm

Duty CycleStandby, Mission Critical, Prime

Maximum Rating3000 kVA (3100 kVA without fan)

Minimum Rating2750 kVA (2850 kVA without fan)

Engine Model3516E, SCAC, V-16, 4-Stroke, Water-Cooled Diesel

Bore6.69in

Stroke8.46in

Displacement4766in

Compression Ratio14:01

AspirationTA

Fuel SystemElectronic unit injection

Governor TypeAdem™ A5

Length - Maximum296.8in

Width - Maximum87.2in

Height - Maximum133.5in

Dry Weight - Genset (maximum)43541lb

Standard

Air cleaner

Single element canister type with service indicator

Optional

Air inlet protection

Heavy duty air cleaners

Remote air inlet adapters

Dual element air cleaners

Standard

Environmental sealed front face

Warning/shutdown with common LED indication of shutdowns for:

Overspeed

RPM

Generator phase sequence

Emergency stop pushbutton

Digital indication for:

Text alarm / event descriptions

2 Programmable digital outputs

Reverse reactive power (kVAr) (32RV)

Reverse power (kW) (32)

Failure to start (overcrank)

Panel lights

Speed adjust

Oil pressure (psi, kPa or bar)

Low coolant level

Generator mounted - rear facing

Over / under frequency (81 o/u)

Lamp test

True RMS AC metering, 3-phase, +/-2% accuracy

Low coolant temperature

Power Factor (per phase & average)

Frequency (Hz)

Overcurrent (50/51)

High coolant temperature

DC volts

6 Programmable digital inputs

Coolant temperature

24 Volt DC operation

Amps (per phase & average)

Emergency stop

Alarm acknowledge

Programmable protective relaying functions:

2 Programmable relay outputs (Form C)

EMCP 4.2B

Serial annunciator module data link

Controls:

kW-hr (total)

kW (per phase, average & percent)

Engine cool-down timer

Operating hours

EMCP 4 Genset Controller

Volts (L-L & L-N)

Engine cycle crank

Communications:

kVAr (per phase, average & percent)

EMCP4.2B controller includes:

Customer data link (Modbus RTU)

Over / under voltage (27/59)

Low oil pressure

kVA (per phase, average & percent)

kVAr-hr (total)

4 Programmable relay outputs (Form A)

Accessory module data link

Standard

Exhaust flange outlet

Standard

Primary fuel filter with integral water separator

Standard

IP23 Protection

Matched to the performance and output characteristics of Cat engines

Standard

Busbar

Optional

Circuit breakers, IEC compliant

Standard

Heavy-duty starting system

Charging alternator

Standard

Caterpillar Extended Life Coolant

Radiator fan and fan drive

Fan and belt guards

JWAC

Coolant drain line with valve

Coolant level sensors

Optional

Optional Serpentine radiators

Water level switch gauges

Heat exchangers

Radiator duct flanges

Standard

Package mounted radiator

Standard

Dry exhaust manifold

Flanged faced outlet(s)

Optional

Mufflers

Through wall installation kit

Flexible fittings

Muffler mounting kits

Standard

Secondary fuel filters

Fuel priming pump

Fuel cooler; not included with packages without radiator

Flexible fuel lines - shipped loose

Optional

Fuel coolers

Primary fuel filter

Standard

Internal excitation

6 Lead

Busbar connections, top center mounted, top cable entry

IEC standard hole pattern

Random wound

3 Phase brushless, salient pole

Winding temperature detectors

NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby).

Generator set packages include Caterpillar's Digital Voltage Regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter

Standard

ADEM III

Standard

English

Standard

Lubricating oil

Oil filter, filler and dipstick

Fumes disposal

Oil drain lines and valve

Gear type lube oil pump

Integral lube oil cooler

Optional

Manual prelube sump pumps

Oil level regulator

Electric prelube pumps

Standard

Rubber anti-vibration mounts (shipped loose)

Rails - engine / generator / radiator mounting

Optional

Spring type vibration isolators

IBC vibration isolators

Standard

Battery and battery rack w/cables

24 Volt electric starting motor

Battery disconnect switch

Optional

Jacket water heaters

ETHER starting aids

Dual 24 volt electric starting motors

24 Volt battery sets - Dry

Charging alternators - 50 Amp

10 and 20 amp battery chargers

Standard

Right hand servicing

Paint: Caterpillar yellow with high gloss black rails & radiator

Flywheel and flywheel housing-SAE No. 00

SAE standard rotation

Optional

Engine barring group

Optional

Cable entry options

Control packaging for enclosures

Optional busbar power connections

EMAX breakers

Load take off; IEC standard hole

Center posts busbars

Trip Units

Optional

External box clips

Local and remote monitoring

Busbar connections

Governors

Generator temperature monitoring

Auxiliary box

Voltage raise / lower switch

EMCP 4.3, EMCP 4.4

EMAX breaker connections

Language options

Remote speed adjust

Annunciator modules

Customer interface options

Vandal proof panel door

Optional

EU declaration of conformity

Optional

3 Phase, Random wound, Internal excitation

Internal excitation

Random wound

Pitch: 0.6667

Optional generators

Number of leads: 6

3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
 

Optional

Thermocouples

Pyrometers and thermocouples

Optional

Explosion relief valves

Optional

PGS test report @ 0.8 power factor

CSA test and certification

Neutral ground certificate

PGS test report @ 1.0 power factor

IBC seismic certificate

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.