G3516C Gas Generator Set

Continuous Rating1660 ekW

Fuel TypeNatural Gas

Maximum Electrical Efficiency37.70%

Maximum Standby Rating1500

Frequency50 / 60 Hz

RPM1500/1800

Engine ModelG3516C

Displacement4210in³

AspirationTA

Bore6.7in

Stroke7.5in

Length219in

Width72in

Height92in

Dry Weight - Genset31226lb

Standard

Two-element single-stage air cleaner with enclosure and service indicator

Optional

Vertical, horizontal dual element air cleaner

Enclosure mounting brackets and piping

Air cleaner with precleaner

Standard

EMCP 4.3

Standard

Jacket water and SCAC driven pumps and bypass lines

2nd Stage SCAC-Cat Flange

Engine driven water pumps for jacket water and aftercooler

Jacket water and SCAC thermostats

ANSI/DN customer flange connections for JW inlet and outlet

Cat flanges on SCAC circuit

Optional

Inlet/Outlet connections

Jacket water coolant heater

Aftercooler air lines, aftercooler core replacement

Standard

Integrated Sensing Module (ISM)

Cat-flanged face outlet on turbocharger

Provides exhaust port temperatures and stack temperature to customer supplied screen via CCM

Dry exhaust manifolds, insulated and shielded

Optional

Flexible Fittings

14" Flange Kit

406 mm Elbow Kits

406 mm flange kits

Mufflers (15/18/25 dBA Attenuation) and spark-arresting muffler with ANSI companion flanges

16" Spark Arresting Muffler

356-406mm Flange and Exhaust Expander

15/18/25 dBA Muffler Attenuation

Standard

24V ETR Gas Shutoff Valve

Engine installed, fuel metering valve

Throttle plate, 24V DC actuator, controlled by ECM

Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve

Fuel Filter

Optional

207-276kPa, 30-40 psi gas knockdown regulator

14-69 kPa (2-10 psi) gas pressure regulator

24VDC Gas Shutoff Valve, Gas Knockdown Regulator

Fuel Filter, Gas Filter

Standard

Individual Cylinder Detonation Sensitive Timing (DST)

Electronic Ignition System (controlled by ECM)

Standard

Electronic fuel metering valve

Standard

Anti-condensation space heater

Busbar connections

Class H Insulation & Class F temperature rise

Reactive Droop

Permanent Magnet Excitation

3-phase brushless, salient pole

Caterpillar's Digital Voltage Regulator (CDVR) with 3-phase sensing and KVAR/PF control

SR4B

Winding temperature detectors

Optional

Cable access box

8.7/15 kV Cross, Differential, Current Transformers (CCCT, DCT, CT)

Medium and high voltage generators and attachment

480/4160/13200 Volt Generator Options (60 Hz)

Generator air filter

Bearing temperature detectors

European Bus Bars

415/400/380, 3300/6600/11000 Volt Generator Options (50 Hz)

Annunciator Modules

Generator Removal

Low voltage extension box

Standard

RH Service

Operation and maintenance manuals

Crankshaft Vibration Damper and Guard

Parts Book

Optional

Special paint order

Tool set

US AID Emblem

Barring group

Digital diagnostic tool

Standard

24V starting motors

Optional

60A, 24V charging alternator (requires engine driven pumps)

Battery removal

20A battery charger

Battery disconnect switch

Battery with cables and rack (shipped loose)

Optional

Local NFPA99-110 Alarm Module w/LEDs

Synchronizing Module

Remote 24V 8/16 Light Annunciator

Engine Failure Relay

PL1000E/PL1000T Communications Module

Custom 8-Light Alarm Module

Optional

Load share module

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.