Voltage/Frequency4000V ± 10%/60 Hz
Type of EX-ProtectionClass 1 Division 2, Group A,B,C,D T3 (NEC or CEC)
Electric Motor TypeSquirrel Cage Induction Motor
Mounting DesignationF1 or F2
Number of Poles8
Full Load Speed894r/min
Connection of Stator WindingStar
Rated Torque29366lb/ft
StandardsNEMA MG1
Maximum Altitude - Before Derate3000ft
Service Factor1.15SF
No Load Current200 Amps
Maximum Ambient Temperature104°F
Temperature RiseClass B at rated load
Shaft8.5in
InsulationClass F
Enclosure Type/Method of CoolingWP-II
DutyContinuous
Locked Rotor Amps520% Code E
Full Load Current658 Amps
Locked Rotor Torque60%
Breakdown Torque190%