ConfigurationConfigurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of OperationMulti-unit Island and multi-unit standby mode with optional redundant controls and components.
ApplicationLV and MV (208V - 38 kV)
ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 50, 51
CertificationsIBC, CBC, UBC & OSHPD Certified
Control Panel EnclosureNEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature0°C to 50°C
Storage Temperature-20°C to +60°C
Low Voltage StandardsNEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage StandardsNEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110